25 November 2023 · Water and wastewater · United States
Aliquippa water authority 2023
A remote pressure station’s Unitronics PLC was taken over from the internet because it answered there on the default port with the default password. The station went to manual. At least 75 devices were hit the same way.
Allegedly state-backedWay in: Device exposed to the internetProcess manipulatedBaseline site
On Saturday 25 November 2023 an alarm sounded at a remote station of the Municipal Water Authority of Aliquippa, Pennsylvania, which regulates water pressure for two neighbouring townships. The screen of its Unitronics Vision PLCProgrammable logic controller: the rugged industrial computer wired to sensors and actuators that runs the automatic control of a machine or process., a controller with the operator display built in, had been replaced with a political message signed CyberAv3ngers.
The authority took the device offline and switched the station to manual operation; CISAThe US Cybersecurity and Infrastructure Security Agency, the government body that publishes advisories and guidance for critical infrastructure. said there was no known risk to the drinking water. It turned out to be one of at least 75 Unitronics devices hit, likely in four waves, between November 2023 and January 2024, 34 of them in the US water sector, with victims in other sectors and countries. A rural group water scheme in County Mayo, Ireland, lost its supply for two days.
Key dates
Way in22 November 2023Attackers begin logging into internet-facing Unitronics PLCsProgrammable logic controller: the rugged industrial computer wired to sensors and actuators that runs the automatic control of a machine or process. with the default password
ImpactSaturday 25 November 2023Alarm at the Aliquippa booster station; the defaced controller is taken offline and the station run by hand
Response28 November 2023CISAThe US Cybersecurity and Infrastructure Security Agency, the government body that publishes advisories and guidance for critical infrastructure. alert names the default password 1111 and port 20256
Response1 December 2023A five-agency advisory alleges the actors are linked to a foreign state; Ireland confirms exploitation
ImpactThrough January 2024The campaign runs on, likely in four waves: at least 75 devices hit, 34 of them in the US water sector
Aftermath2 February 2024US Treasury sanctions six officials it alleges were behind the campaign
Aftermath7 August 2024The US State Department offers up to $10 million for information on the same six officials
Aftermath7 April 2026A joint advisory on new attacks on US controllers recalls the CyberAv3ngers campaign
How did that happen
The way in, and the way through
There was no exploit. The actors probed the internet for devices answering on TCP port 20256, the Unitronics default, and logged in with the vendor’s default password, 1111, or found devices with no password at all. The weakness was later assigned CVE-2023-6448. Once in, they uploaded a defacement page to the HMIHuman-machine interface: the operator screen or panel used to watch a process and adjust it, usually sitting in front of a PLC or a SCADA system., erased the ladder logicThe graphical programming language used in most PLCs, drawn as rungs of a ladder that mimic the relay wiring diagrams electricians know., renamed devices, changed the port and disabled uploads, which left operators without their normal view of inputs and outputs.
The campaign was opportunistic: the attackers picked one maker’s controllers to carry their message, not this plant. Any small operator with the same controller on the internet was a target.
The path through the plant, step by step (the numbers are the steps told below)
Attribution: Actors using the CyberAv3ngers persona. Five government agencies allege links to a foreign state (joint advisory AA23-335A); the US Treasury sanctioned six officials over the campaign on 2 February 2024 and the US offered a reward of up to $10 million for information on them in August 2024. These are allegations, not tested in court
The sequence of events
How it unfolded, step by step
The record in order, from the first foothold to the recovery. Each step says what was done, how it worked, what it looked like from inside the plant, and where the attacker was in the plant at that moment. Read this first; the game that follows asks what would have stopped each step.
1
Stage 1 · ReconnaissanceInternetNovember 2023, before the 22nd
Scanning the internet for Unitronics PLCs on port 20256
The actors did not need to know anything about Aliquippa. They probed public internet addresses for anything that answered on TCP port 20256, the port Unitronics controllers use by default, and every device that replied went on the list. Unitronics Vision controllers are common in small water systems, where they run pumps, dosing and alarms with the operator screen built into the same box.
Many of those controllers had been put on the internet on purpose, so that staff or the integrator could reach them from home. Whether the authority had a list of which of its stations answered from the internet is not known; what is clear is that nothing closed the exposure before the scanners found it.
How long the probing went on, or how many devices it listed, is not on record either; the advisory says only that the first logins came on 22 November. By then the actors knew exactly which doors to try.
“Cyber actors are actively targeting TCP 20256 after identifying it through network probing as a port associated to Unitronics PLC.”
1The controller answers straight from the internet on its default port.
2The actors scan the internet for the controllers that reply.
3Every device that answers goes on the target list.
2
Stage 1 · ExploitationField devicesFrom 22 November 2023
Logging in with the default password, or none
A Unitronics controller that answers on its default port is protected by a password, if one has been set. The factory setting is 1111, and some devices had no password at all. The actors typed it in and were through: no software flaw, no exploit, just the same login an engineer with the programming software would use.
What the authority could see at this point, if anything, is not recorded. A login with the correct password looks like any other login, and nothing stood between the internet and the controller’s administrative interface. On the devices hit, the factory password had never been changed, or none had ever been set.
The weakness was later recorded as CVE-2023-6448, a default administrative password in VisiLogic, the Unitronics programming software, before version 9.9.00. With it the actors held the same rights as the integrator, including the right to rewrite the program the station runs on.
“The actors compromised multiple Unitronics Vision Series devices by authenticating to internet-connected devices with communications set to the default TCP port 20256. These devices either had a default password in place or no password.”
Once in, the actors uploaded a splash page carrying their political message to the controller’s screen, so operators could no longer read the inputs and outputs it normally shows. They erased the ladder logicThe graphical programming language used in most PLCs, drawn as rungs of a ladder that mimic the relay wiring diagrams electricians know., the program that runs the station, and loaded one of their own that had no inputs or outputs. They renamed the device, moved its port from 20256 to 20257 and switched off the upload and download functions.
For the engineers at the sites hit this meant the controller could no longer be reached the way it always had been: the remote connection needs the device name, and the port had moved. The original program had been erased from the device, so getting a station back meant matching the workstation software to what the actors had set or factory resetting the device, then reloading the program, if a copy of it existed anywhere but on the device.
On a Vision controller the screen and the controller are one device, so the same access that changed the display could have changed set pointsThe target value an operator or a program gives a controller, such as the temperature or pressure it must hold.. Whether that happened at Aliquippa is not stated; the authority reported no known risk to the drinking water.
Inside the plant: At hit sites the controller’s display showed the group’s message in place of the normal readings, and engineering connections were refused until the device was factory reset or the workstation software matched what the actors had set.
“The actors compromised at least 75 devices, including at least 34 in the WWS Sector in the United States.”
1Whoever is logged in can rewrite the controller’s program and settings.
2They deface the screen and wipe the controller’s logic.
3Operators lose their normal view and control of the station.
4
Stage 2 · ImpactPhysical processSaturday 25 November 2023
Alarm at the pressure station; system taken offline and run by hand
At Aliquippa the intrusion hit a booster station on the outskirts of town that monitors and regulates water pressure for Raccoon and Potter townships. The authority disabled the compromised controller and crews switched the station to manual operation.
State police opened a criminal investigation and CISAThe US Cybersecurity and Infrastructure Security Agency, the government body that publishes advisories and guidance for critical infrastructure. responded. There was no known risk to the drinking water or the supply: the station could be run by hand, which is what kept a defaced controller from becoming a supply problem.
What the day exposed was that the station rested on a single controller, reached from the internet, and that nothing had found the exposure before the actors did. The US Treasury later said the incidents were quickly remediated with minimal impacts.
Inside the plant: An alarm went off at the station as soon as the hack occurred; the authority disabled the system and state police were called to the booster station on the Saturday (CBS News Pittsburgh).
“In response, the affected municipality’s water authority immediately took the system offline and switched to manual operations.”
1The station rests on one controller, reached from the internet.
2An alarm sounds; crews disable it and run the station by hand.
3Manual operation keeps the defaced controller off the supply.
5
Stage 2 · Response and recoveryIT to OT boundary28 November to 1 December 2023
CISA alert, then a five-agency advisory; Ireland and the UK warn operators
On 28 November CISAThe US Cybersecurity and Infrastructure Security Agency, the government body that publishes advisories and guidance for critical infrastructure. published an alert that named the default password 1111 and port 20256 and told operators what to do: change the password, take the controller off the open internet, put a firewall or VPNVirtual private network: an encrypted tunnel over the internet that makes a remote computer behave as if it were plugged into the plant or office network. in front of it and back up the logic. On 1 December CISA, the FBI, the National Security Agency, the Environmental Protection Agency and a fifth national agency issued joint advisory AA23-335A, alleging that the actors were linked to a foreign state. Ireland’s National Cyber Security Centre (NCSC) confirmed active exploitation in Ireland the same day; the UK NCSC had warned providers on 30 November.
For many operators a government alert was the first they knew of it. Many had no routine for reading sector alerts and no list to check against, so whether a utility closed the door in time depended on whether somebody read a government bulletin that week. The campaign ran on, likely in four waves, into January 2024, and reached at least 75 devices, 34 of them in the US water sector.
In Ireland, press reported a private group water scheme in Erris, County Mayo, without supply for two days after its pumping system was hit; the link to the campaign rests on the message left on its screen. On 2 February 2024 the US Treasury sanctioned six officials it alleges were behind the campaign.
Inside the plant: In County Mayo an employee found a “You have been hacked” message on the pumphouse computer screen; the scheme restored supply by hand on the Friday night, after about two days without water (press, via The Record and WaterISAC).
“Ensure the Unitronics PLC default password “1111” is not in use.”
The same steps, as decisions. At most steps you pick the control that would have stopped the attack at a cost a baseline site can carry; at some you place the attacker on the plant map first, or spot the one control that does not act. A nuclear-grade answer at a water utility scores less than the right-sized one, because the money and the people are not infinite. Round 2 hands you a budget. “Would have stopped” means in this exercise’s judgement, with the control in place and working; the record rarely says what the operator actually had, and no control is a guarantee.
Step 1 of 5
0 / 15 shield0 / 2 insight
Baseline site · the band this exercise judges by
A small municipal water authority: a handful of staff, remote pressure stations, an integrator on call. What it is reasonable to expect is hygiene, the CISA performance goals, not an OT security operations centre.
Target security levels come from the site's own IEC 62443-3-2 risk assessment; these bands are how the game judges what is proportionate. The reasoning under each answer says why a control is the right weight for this site.
01
Stage 1 · ReconnaissanceNovember 2023, before the 22nd
Scanning the internet for Unitronics PLCs on port 20256
1The controller answers straight from the internet on its default port.
2The actors scan the internet for the controllers that reply.
3Every device that answers goes on the target list.
Scanning the internet for devices on the Unitronics port
Unitronics Vision controllers are common in small water utilities for pump control, dosing and alarms, and are often put on the internet so staff and the integrator can reach them. The actors built their target list by probing the internet for devices answering on the Unitronics default port. Re-read this step in the story
Before the control: where in the plant was the attacker at this step? 1 insight point
02
Stage 1 · ExploitationFrom 22 November 2023
Answer the step above
Logging in with the default password, or none
03
Stage 2 · Execute ICS attack22 to 25 November 2023
Alarm at the pressure station; system taken offline and run by hand
05
Stage 2 · Response and recovery28 November to 1 December 2023
Answer the step above
CISA alert, then a five-agency advisory; Ireland and the UK warn operators
Scoring: 3 points for the proportionate control, 2 for one that works but is heavier than this site needs, 1 for a control that helps, 0 for one that does not act at that step. In an odd-one-out step, 3 points for spotting the control that does not act. Plant-map questions earn insight points. Sources are listed at the end of the page. Jump to sources
Response and recovery
How they got back
Aliquippa disabled the compromised controller and ran the station manually while the investigation ran; there was no known risk to the drinking water. The Irish scheme had its supply restored after two days. CISAThe US Cybersecurity and Infrastructure Security Agency, the government body that publishes advisories and guidance for critical infrastructure.’s mitigations were short and specific: take PLCsProgrammable logic controller: the rugged industrial computer wired to sensors and actuators that runs the automatic control of a machine or process. off the open internet, replace default passwords, require MFAMulti-factor authentication: a login that needs something more than a password, such as a code from a phone or a hardware key, so a stolen password alone is not enough. for remote access to the OT network, change the default port, back up the ladder logicThe graphical programming language used in most PLCs, drawn as rungs of a ladder that mimic the relay wiring diagrams electricians know. and update VisiLogic to 9.9.00, which no longer ships with a default password. Treasury said the incidents were quickly remediated with minimal impacts.
Take this to your plant
1Find every device that answers from the internet before someone else does: an inventory and a scan of your own public addresses, once a quarter.
2Default passwords are the attack. Change them at commissioning, and write down that you did.
3For a small site the proportionate answer is hygiene plus a manual fallback and a backup of the logic, not a monitoring platform. Spend the money on the fix, not the alarm.
Sources
Where this record comes from
Government advisories, the victim's own statements, court and parliamentary records, and the technical reports of the teams that analysed the malware. Press is used only where no primary record exists, and is marked.
The 25 November date and the station’s role (pressure for Raccoon and Potter townships) come from press reports; the government documents describe “a U.S. water facility” and say the campaign began on 22 November 2023.
The Irish outage is press-only: The Record reports about 160 households without water for two days on a private group water scheme in Erris, County Mayo; WaterISAC, citing the Western People, reports 180 homeowners on the Binghamstown/Drum scheme and says supply was restored manually. Its link to the CyberAv3ngers campaign rests on press reports of the message left on the system; Ireland’s NCSC confirmed active exploitation in Ireland without naming the scheme.
The device counts (at least 75, at least 34 in US water) and the four likely waves come from the December 2024 update of AA23-335A, not the original 1 December 2023 advisory.
Whether set points were changed at Aliquippa is not stated; the authority reported no known risk to the drinking water or supply.