8 April 2022 (disclosed 12 April 2022) · Electricity transmission · Ukraine

Industroyer2: the attack that was stopped 2022

Attackers that CERT-UA and ESET identify as Sandworm built a new version of the Industroyer grid malware, Industroyer2, carrying the specific addresses of a Ukrainian energy provider’s own high-voltage substations, and scheduled it to cut power on the evening of 8 April 2022. CERT-UA and ESET stopped it before any breaker opened, and no outage occurred.

Allegedly state-backedWay in: Not publicly confirmedStopped before impactHigh-consequence site

What happened

The short version

In April 2022 CERT-UA, Ukraine’s government cyber incident response team, responded with ESET and Microsoft to a targeted attack on a regional Ukrainian energy provider. The attackers, the Sandworm group, had built a new version of the Industroyer grid malware, named Industroyer2, and configured it with the specific parameters of the victim’s own high-voltage substations. The destructive actions were scheduled for the evening of Friday 8 April; the attack was detected and stopped before any breaker opened, and no loss of supply occurred. A Ukrainian official put the population of the area served at about two million (press).

Alongside Industroyer2 the attackers staged wipersMalware whose only purpose is to destroy data or make computers unbootable, with no ransom and no way back except restoring from backup. to destroy the environment and slow recovery: CaddyWiper for Windows machines (user computers, servers and ICSIndustrial control system: the general term for the controllers, networks and software that run physical processes, covering SCADA, DCS and PLC systems. workstations) and the Bash scripts ORCSHRED, SOLOSHRED and AWFULSHRED for Linux and Solaris servers, with active network equipment also on the target list. CERT-UA said the victim suffered two waves of attacks and that the initial compromise occurred no later than February 2022. It thanked Microsoft and ESET. This is the library’s one example of an ICS attack that was detected and stopped.

Key dates

  1. Way inNo later than February 2022The energy provider is compromised; the entry route is never made public
  2. PreparationFebruary to April 2022Attackers tunnel between network segments toward the control network
  3. Preparation23 March 2022Industroyer2 is built, carrying the victim’s own substation addresses
  4. Impact8 April 2022, 16:10 UTCIndustroyer2 is scheduled to open breakers, with a wiperMalware whose only purpose is to destroy data or make computers unbootable, with no ransom and no way back except restoring from backup. set for ten minutes later
  5. ResponseBy 8 April 2022The attack is stopped before any breaker opens; how and when it was detected is not public
  6. Aftermath12 April 2022CERT-UA and ESET publicly disclose the thwarted attack

How did that happen

The way in, and the way through

How the attackers first got in, and how they crossed from the IT network into the ICSIndustrial control system: the general term for the controllers, networks and software that run physical processes, covering SCADA, DCS and PLC systems. network, is not established in the public record: ESET stated plainly that it did not know, and CERT-UA gave only that the initial compromise was no later than February 2022. What is recorded is that they moved between network segments using chains of SSH tunnels, ran commands remotely with Impacket, and, ESET believed, had working credentials in hand before the attack.

Industroyer2 was a single Windows executable, compiled on 23 March 2022, that spoke only one protocol, IEC 60870-5-104IEC 104 for short: the protocol electricity grid control centres use to monitor and command substations, with no built-in check on who is sending. (IEC 104), used to talk to substation equipment such as protection relays and RTUsRemote terminal unit: a small controller at an outlying site such as a pump station or substation that reports readings and takes commands over a telemetry link.. Its configuration was hardcoded into the file: the target device addresses, the IEC 104 ASDU and Information Object AddressesInformation object address: the number that identifies a single point, such as one circuit breaker, in an IEC 104 message between a control centre and a substation. (IOAs, the specific control points), and the ON or OFF state to command at each, which Mandiant mapped to power line switches or circuit breakers. Because it was compiled for this one environment, each executable carried the unique parameters of the substations it was meant to operate. A scheduled task was set to run it at 16:10 UTC on 8 April, with CaddyWiper set to run ten minutes later to erase its traces.

The path through the plant, step by step (the numbers are the steps told below)

Attribution: Attributed by Ukraine’s CERT-UA to Sandworm, which it tracks as UAC-0082. ESET assessed with high confidence that Sandworm was responsible. The US Department of Justice alleges that Sandworm is part of a foreign military intelligence service and indicted six officers in 2020 for earlier operations, including the 2016 Industroyer attack, not for this 2022 attempt. These are allegations, not tested in court.

The sequence of events

How it unfolded, step by step

The record in order, from the first foothold to the recovery. Each step says what was done, how it worked, what it looked like from inside the plant, and where the attacker was in the plant at that moment. Read this first; the game that follows asks what would have stopped each step.

  1. Stage 1 · DeliveryEnterprise ITNo later than February 2022 (CERT-UA)

    Initial compromise, by a route not made public

    How the attackers first got into the energy provider’s network is not known, and the investigators said so plainly: ESET did not know how the first victim was compromised, and CERT-UA gave only that the break-in had happened by February 2022 at the latest. A later US laboratory study put first access no later than 17 February, likely through an internet-facing device such as a corporate workstation, without settling the route.

    That silence is the honest state of the record: where many write-ups would reach for a phishing emailAn email or message that tricks someone into opening an attachment, clicking a link or giving up a password; spear-phishing is the same thing aimed at a named person., here nobody could show one. The lesson is not a clever trick. A capable state team was inside for roughly two months before the destructive day, and when in that time it was found is not public either. With no route to point at, what an operator can do is make sure the usual doors are shut and that one foothold cannot reach the plant.

    1. 1A capable state team sets its sights on the energy provider.
    2. 2It gets in by a route never made public.
    3. 3The intruders sit inside the network for roughly two months.
  2. Stage 1 · Lateral movementIT to OT boundaryBetween February and April 2022

    Moving between network segments toward the ICS

    Over the weeks that followed, the attackers worked their way across the internal network toward the systems that control the grid. CERT-UA described them hopping between network segments through chains of SSH tunnels (SSH, Secure Shell, is the encrypted remote login that Linux and Unix servers use) and running commands on remote machines. ESET believed they already held working credentials, which is how the Linux and Solaris wiperMalware whose only purpose is to destroy data or make computers unbootable, with no ransom and no way back except restoring from backup. that came later could spread by trying logins over SSH.

    How they crossed from the ordinary IT network into the industrial control network is another thing ESET said it did not know. Whatever the exact path, the tunnels crossed whatever boundaries stood between the segments, and no alarm on the internal SSH traffic is mentioned anywhere: the move toward the substations was not stopped on the way.

    “Можливість горизонтального переміщення між сегментами локальної обчислювальної мережі забезпечено шляхом створення ланцюгів SSH-тунелів.”

    Source 1: Кібератака групи Sandworm (UAC-0082) на об’єкти енергетики України з використанням шкідливих програм INDUSTROYER2 та CADDYWIPER (CERT-UA#4435)
    1. 1Credentials and a path between network segments are already in hand.
    2. 2The attackers tunnel between segments with credentials in hand.
    3. 3They reach the control network, unstopped on the way.
  3. Stage 2 · Deliver ICS payloadControl networkIndustroyer2 compiled 23 March 2022, staged for 8 April

    Industroyer2 built for these substations

    The weapon was a single Windows program, built on 23 March, that spoke just one language: IEC 104IEC 104 for short: the protocol electricity grid control centres use to monitor and command substations, with no built-in check on who is sending., the protocol used to talk to substation equipment such as protection relays. Everything it needed was written into the file itself: the addresses of the target devices, the exact control points, and whether to command each one on or off. Because the settings were baked in, the attackers built a copy for this one site, carrying its own substations’ addresses.

    That design made it dangerous, and it relied on a weakness in the protocol itself. IEC 104IEC 104 for short: the protocol electricity grid control centres use to monitor and command substations, with no built-in check on who is sending. checks nothing about who is talking: any machine that can reach the relays and speak the protocol is treated as a legitimate controller. A prepared attack host, placed where it could reach the devices, would look no different from the normal control server to anyone who was not watching for a new talker. The program even shut down a legitimate process used in daily operations and renamed its file so it could not restart.

    “кожен виконуваний файл містив статично вказаний набір унікальних параметрів для відповідних підстанцій”

    Source 1: Кібератака групи Sandworm (UAC-0082) на об’єкти енергетики України з використанням шкідливих програм INDUSTROYER2 та CADDYWIPER (CERT-UA#4435)
    1. 1The grid protocol checks nothing about who is talking.
    2. 2Malware is built to speak that protocol to named substations.
    3. 3A rogue host now passes as the normal control server.
  4. Stage 2 · Execute ICS attackField devices8 April 2022, scheduled for 16:10 UTC (Friday evening)

    Set to open the breakers, then stopped

    A scheduled task was set to run Industroyer2 at 16:10 UTC (Coordinated Universal Time) on Friday 8 April, timed for the evening as people came home. Its job was to send the IEC 104IEC 104 for short: the protocol electricity grid control centres use to monitor and command substations, with no built-in check on who is sending. commands that open breakers and cut power across a region; a Ukrainian official later put the area served at about two million people. Ten minutes behind it, a wiperMalware whose only purpose is to destroy data or make computers unbootable, with no ransom and no way back except restoring from backup. was scheduled to erase the traces.

    The attack was stopped before any breaker opened, and no supply was lost. Whether the program ran at its hour is not settled; what is settled is that the breakers stayed closed. That leaves a question the public account cannot answer: had the commands gone through, was there anything at the substations, outside the software that sent them, that would have kept a malicious switching operation from doing lasting damage.

    “Scheduled execution of Industroyer2 to cut power in an Ukrainian region”

    Source 2: Industroyer2: Industroyer reloaded
    1. 1A scheduled command can open the breakers from the control host.
    2. 2A timer is set to open the breakers one Friday evening.
    3. 3The attack is stopped before any breaker opens.
  5. Stage 2 · ImpactControl network8 April 2022, staged alongside Industroyer2

    Wipers staged to destroy the environment and slow recovery

    Alongside the grid malware the attackers planted wipersMalware whose only purpose is to destroy data or make computers unbootable, with no ransom and no way back except restoring from backup.: CaddyWiper to destroy Windows machines, including the one that would run Industroyer2, and scripts to wipe Linux and Solaris servers. ESET judged these were meant to slow recovery and to keep operators from getting their control screens back, turning a short attack into a long outage.

    Staged from inside with the attackers’ own access, the wipersMalware whose only purpose is to destroy data or make computers unbootable, with no ransom and no way back except restoring from backup. would have met little resistance on the day. What backups or rebuild plan the provider had is not on record. What decides a day like this is unglamorous: whether the plant can get its servers, screens and device settings back quickly from somewhere the attackers could not reach, not another layer at the perimeter.

    “We believe it was intended to slow down the recovery process and prevent operators of the energy company from regaining control of the ICS consoles.”

    Source 2: Industroyer2: Industroyer reloaded
    1. 1No one knows if clean, offline backups exist to rebuild from.
    2. 2Wipers are planted to destroy the servers and control screens.
    3. 3A wiper that ran would stretch this into a long outage.
  6. Stage 2 · Response and recoveryControl network8 April 2022 (the time of detection is not public)

    Detected and stopped before it cut power

    The attack was caught and stopped before it cut power. CERT-UA, working with ESET and Microsoft, responded and prevented the plan, and the provider kept supply. How it was first spotted was never disclosed: a Ukrainian official declined to say how it was defeated, and the technical reports describe the response and the outcome, not the trigger.

    What the reports do note is that Industroyer2 hid nothing, carrying its settings in plain text so it was readable once found, and that some detection rules written for the 2016 Industroyer recognised the new version. The defensible lesson is not one lucky catch but a standing capability: being able to see what is happening on the control network, knowing in advance who does what and whom to call, and having something safe to rebuild from, all in place inside the two months or so the intruders were in the network.

    1. 1How the attack is first spotted is never disclosed.
    2. 2Responders catch the staged attack before its set hour.
    3. 3No breaker opens; supply holds and no power is lost.

That is the record. Now the question each step raises:

Could you have stopped it?

Now you decide

Could you have stopped it?

The same steps, as decisions. At most steps you pick the control that would have stopped the attack at a cost a high-consequence site can carry; at some you place the attacker on the plant map first, or spot the one control that does not act. A nuclear-grade answer at a water utility scores less than the right-sized one, because the money and the people are not infinite. Round 2 hands you a budget. “Would have stopped” means in this exercise’s judgement, with the control in place and working; the record rarely says what the operator actually had, and no control is a guarantee.

Step 1 of 6
0 / 18 shield 0 / 1 insight
High-consequence site · the band this exercise judges by

National and regional electricity transmission: high-voltage substations serving an area CERT-UA would not size but a Ukrainian official put at about two million people. This is high-consequence infrastructure where investment in assurance against a capable state adversary is justified, the opposite end of the scale from a town water station.

Target security levels come from the site's own IEC 62443-3-2 risk assessment; these bands are how the game judges what is proportionate. The reasoning under each answer says why a control is the right weight for this site.
01
Stage 1 · DeliveryNo later than February 2022 (CERT-UA)

Initial compromise, by a route not made public

  1. 1A capable state team sets its sights on the energy provider.
  2. 2It gets in by a route never made public.
  3. 3The intruders sit inside the network for roughly two months.

Getting in by a route never made public

CERT-UA stated that the victim suffered two waves of attacks and that the initial compromise occurred no later than February 2022, but did not state the vector. ESET said it did not know how the attackers compromised the initial victim. This step is here so the walkthrough does not pretend the entry point is known; where the record is silent, it is left silent. Re-read this step in the story

Before the control: where in the plant was the attacker at this step? 1 insight point

02
Stage 1 · Lateral movementBetween February and April 2022
Answer the step above

Moving between network segments toward the ICS

03
Stage 2 · Deliver ICS payloadIndustroyer2 compiled 23 March 2022, staged for 8 April
Answer the step above

Industroyer2 built for these substations

04
Stage 2 · Execute ICS attack8 April 2022, scheduled for 16:10 UTC (Friday evening)
Answer the step above

Set to open the breakers, then stopped

05
Stage 2 · Impact8 April 2022, staged alongside Industroyer2
Answer the step above

Wipers staged to destroy the environment and slow recovery

06
Stage 2 · Response and recovery8 April 2022 (the time of detection is not public)
Answer the step above

Detected and stopped before it cut power

Scoring: 3 points for the proportionate control, 2 for one that works but is heavier than this site needs, 1 for a control that helps, 0 for one that does not act at that step. In an odd-one-out step, 3 points for spotting the control that does not act. Plant-map questions earn insight points. Sources are listed at the end of the page. Jump to sources

Response and recovery

How they got back

There was no outage to recover from: the provider kept supply. CERT-UA, with ESET and Microsoft, remediated the network, and CERT-UA shared indicators of compromise, Yara rulesA way of writing text rules that describe what a piece of malware looks like, so security tools can search files and memory for it. and samples (restricted, TLPTraffic Light Protocol: colour labels (red, amber, green, clear) on shared threat information that say how widely it may be passed on.:AMBER) with a limited circle of international partners and Ukrainian energy companies. The lasting significance is twofold. It showed that known OT malware can be recompiled and reused against a new victim, which Mandiant called the first such instance. And it is the clearest public case of a grid attack caught and stopped before it cut power. Because how it was detected was not disclosed, the lesson is less any single clever catch than the standing capability, the monitoring, the response relationships and the rehearsed recovery, that let a capable attack be found inside the two months or more it sat in the network.

Take this to your plant

  • 1Monitoring that baselines OT traffic is what finds a new host talking IEC 104IEC 104 for short: the protocol electricity grid control centres use to monitor and command substations, with no built-in check on who is sending. to the relays, and a scheduled task, before the hour it is set for. Industroyer2 was caught before it cut power; that is the whole lesson.
  • 2The malware was recompiled for this one environment, carrying the victim’s own substation addresses. Known OT tooling can be reused against a new target, so segmentation, configuration and logic integrity, and backups matter even against a tool everyone has already analysed.
  • 3The record never says how it was detected. The defensible lesson is the standing capability behind a fast joint response: OT visibility, a rehearsed incident plan, protected backups, and the relationships to call in national and vendor help.

Sources

Where this record comes from

Government advisories, the victim's own statements, court and parliamentary records, and the technical reports of the teams that analysed the malware. Press is used only where no primary record exists, and is marked.

  1. 1
  2. 2
    Industroyer2: Industroyer reloaded ESET (WeLiveSecurity), 2022 · Vendor technical report
  3. 3
    INDUSTROYER.V2: Old Malware Learns New Tricks Mandiant (Google Cloud), 2022 · Vendor technical report
  4. 4
    Industroyer2: Nozomi Networks Labs Analyzes the IEC 104 Payload Nozomi Networks Labs, 2022 · Vendor technical report
  5. 5
  6. 6
  7. 7
    Report on the thwarted attack on the Ukrainian grid (April 2022) Associated Press (Frank Bajak), via News4Jax, 2022 · Press
  8. 8
    Precursor Analysis Report: Industroyer2 and Wiper Malware Targeting Ukrainian Energy Provider 2022 (INL/RPT-23-71546) Idaho National Laboratory, CyOTE programme (US DOE CESER), 2023 · Research institute analysis
Where the record is uncertain
  • How the attackers first got in, and how they crossed from the IT network into the ICS network, is not public. CERT-UA stated only that the initial compromise was no later than February 2022; ESET said it did not know. Any account of the vector would be speculation.
  • How the attack was detected and stopped is not disclosed. CERT-UA reported only the outcome (prevented) and thanked ESET and Microsoft; a Ukrainian official declined to say how it was defeated (press). The detection step is deliberately thin because the record is.
  • Whether the Industroyer2 executable actually ran at the scheduled hour is not settled. ESET’s timeline lists its scheduled execution at 16:10 UTC and elsewhere refers to the machine where Industroyer2 was executed; CERT-UA said only that the plan was prevented, and no outage was reported. The record supports that it was stopped before any breaker opened, not necessarily before the file ran.
  • The victim is not named. The figure of about two million people in the area served comes from Ukraine’s deputy energy minister via press (AP: 2 million; Wired: more than 2 million), not from a technical report. An early, unpublished CERT-UA note reported in the press mentioned nine substations briefly de-energised; CERT-UA and officials later stood by the public account that the attack was prevented and called the earlier note preliminary.
  • The number of substations targeted was not released (authorities cited security concerns, per AP). The sample ESET analysed held eight device addresses; samples examined by Nozomi and Mandiant held three and eight, so the device counts are per-sample, not a substation total.