29 December 2025 · Renewable generation and combined heat and power · Poland

Poland’s energy sector 2025

In one coordinated day an attacker bricked field devices at more than 30 wind and solar farms through their factory logins, ran a wiper at a large heat and power plant and stopped the controllers at a smaller one. Generation continued, and EDR halted the wiper part-way.

Allegedly state-backedWay in: Remote access (VPN, remote desktop)Physical damageStructured site

What happened

The short version

On 29 December 2025 an attacker struck Poland’s energy sector in a coordinated, partly automated operation. At more than 30 wind and solar farms it logged in to the field equipment at the grid connection points, remote terminal unitsRemote terminal unit: a small controller at an outlying site such as a pump station or substation that reports readings and takes commands over a telemetry link., protection relays, serial servers and local HMIsHuman-machine interface: the operator screen or panel used to watch a process and adjust it, usually sitting in front of a PLC or a SCADA system., and destroyed it: firmwareThe built-in software inside a device such as a PLC, switch or firewall, below the user programs, which the maker updates from time to time. corrupted, system files deleted, devices reset and pointed at nowhere. The farms lost their link to the distribution system operator and could no longer be controlled remotely, but they kept generating.

The same day a wiperMalware whose only purpose is to destroy data or make computers unbootable, with no ransom and no way back except restoring from backup. ran across a large combined heat and power plant that supplies heat to almost half a million customers, until the plant’s EDREndpoint detection and response: security software on each PC and server that watches for attacker behaviour, not just known viruses, and lets a team investigate and contain it. product stopped it, and at a smaller CHP plant the attacker stopped the controllers and locked them with a password of its own, shutting down a steam turbine and water treatment. A manufacturer was hit with a wiper too. Electricity production was not affected, and at the large plant the attack did not achieve its aim of disrupting heat supply.

Key dates

  1. Way inMarch to May 2025First attacker activity at the large CHP plant: a VPNVirtual private network: an encrypted tunnel over the internet that makes a remote computer behave as if it were plugged into the plant or office network. login, a jump hostA single hardened computer that remote users must log in to first, so every session into the plant passes through one controlled and recorded door., then the domain controllerThe server that runs Active Directory for a Windows domain and checks every login, which is why attackers aim for it first.
  2. PreparationJuly 2025The plant’s entire Active DirectoryThe Microsoft system that holds every user account, password and computer in a Windows domain, so whoever controls it controls every machine in it. database is copied
  3. Preparation8 December 2025At renewable sites, operator HMIsHuman-machine interface: the operator screen or panel used to watch a process and adjust it, usually sitting in front of a PLC or a SCADA system. are opened up for remote execution
  4. Preparation18 to 25 December 2025A wind farm’s private cellular network is scanned; a smaller CHP plant is reconnoitred through it
  5. Impact29 December 2025Coordinated destruction at more than 30 farms, two CHP plants and a manufacturer
  6. Response29 December 2025EDREndpoint detection and response: security software on each PC and server that watches for attacker behaviour, not just known viruses, and lets a team investigate and contain it. halts the wiperMalware whose only purpose is to destroy data or make computers unbootable, with no ransom and no way back except restoring from backup. at the large CHP plant; electricity production continues throughout
  7. Aftermath13 to 15 January 2026Ministers disclose the attack; the Prime Minister points to groups linked to foreign services
  8. AftermathLate January 2026CERT Polska publishes its report; ESET and Dragos publish their attributions

How did that happen

The way in, and the way through

The ways in were the edge devices: FortiGate firewalls doubling as VPNVirtual private network: an encrypted tunnel over the internet that makes a remote computer behave as if it were plugged into the plant or office network. concentrators, with the VPN interface open to the internet and accounts that needed only a password. At the large CHP plant the attacker logged in as early as spring 2025, reached a jump hostA single hardened computer that remote users must log in to first, so every session into the plant passes through one controlled and recorded door. through saved remote-desktop credentials, took the domain controllerThe server that runs Active Directory for a Windows domain and checks every login, which is why attackers aim for it first. and in July copied the entire Active DirectoryThe Microsoft system that holds every user account, password and computer in a Windows domain, so whoever controls it controls every machine in it. database. At the farms CERT Polska thinks the attacker gained administrative rights on the devices and with them the VPN credentials for every subnet behind them; it notes that the same credentials are often reused from site to site.

Inside, the field devices were taken with factory-default logins: a default web account to upload corrupted firmwareThe built-in software inside a device such as a PLC, switch or firewall, below the user programs, which the maker updates from time to time. to Hitachi RTU560 units, default root SSH on Mikronika units, a default FTP account on Hitachi Relion protection relays, default passwords on Moxa serial servers and on Windows HMIsHuman-machine interface: the operator screen or panel used to watch a process and adjust it, usually sitting in front of a PLC or a SCADA system.. A second route ran through a wind farm’s cellular router into a private APN, where a controller with a default admin password opened the way into the smaller CHP plant. At the large plant the wiperMalware whose only purpose is to destroy data or make computers unbootable, with no ransom and no way back except restoring from backup. was pushed to machines by a new group policyThe Active Directory feature for pushing settings or software to every computer in a domain at once, which attackers can abuse to spread malware the same way..

The path through the plant, step by step (the numbers are the steps told below)

Attribution: Alleged, not established. Poland’s Prime Minister said the attacks were prepared by groups linked to foreign services. CERT Polska links the infrastructure to the cluster known as Static Tundra, Berserk Bear or Dragonfly, which the US FBI alleges belongs to a foreign intelligence service; ESET attributes the wiper to Sandworm with medium confidence and Dragos the operation to ELECTRUM with moderate confidence

The sequence of events

How it unfolded, step by step

The record in order, from the first foothold to the recovery. Each step says what was done, how it worked, what it looked like from inside the plant, and where the attacker was in the plant at that moment. Read this first; the game that follows asks what would have stopped each step.

  1. Stage 1 · ExploitationIT to OT boundarySpring to December 2025

    VPN logins that asked only for a password

    Every site in this attack had the same kind of front door. A FortiGate device sat at the edge doing two jobs, firewall and VPNVirtual private network: an encrypted tunnel over the internet that makes a remote computer behave as if it were plugged into the plant or office network. concentrator, and its VPN interface answered anyone on the internet. The accounts it accepted were defined on the device itself and needed nothing but a password. CERT Polska notes that some of these devices had had remote code execution flaws in the past, and that reusing the same credentials from site to site is common in the industry.

    At the large CHP plant the record is clearest. Several SSL-VPN accounts were statically defined without two-factor authenticationMulti-factor authentication: a login that needs something more than a password, such as a code from a phone or a hardware key, so a stolen password alone is not enough., and the logs showed logins through TorA network that hides where internet traffic comes from by bouncing it through several volunteer-run relays, used by attackers to stay anonymous. and from Polish and foreign addresses. Saved remote-desktop bookmarks carried their own target credentials, so a VPNVirtual private network: an encrypted tunnel over the internet that makes a remote computer behave as if it were plugged into the plant or office network. login led straight to a jump hostA single hardened computer that remote users must log in to first, so every session into the plant passes through one controlled and recorded door.. At the manufacturer, the firewall’s configuration had been stolen and posted on a criminal forum, and the attacker came in with credentials obtained earlier.

    Nothing here needed a new exploit. A password that worked once worked everywhere it had been reused, and a VPNVirtual private network: an encrypted tunnel over the internet that makes a remote computer behave as if it were plugged into the plant or office network. that asks for nothing else hands over every subnet behind it.

    “was accessible from the Internet and allowed authentication using accounts defined in the device configuration”

    Source 2: Energy Sector Incident Follow-up Report 2025
    1. 1A firewall at the farm also runs the VPN, open to the internet.
    2. 2An account that needs only a password lets the attacker in.
    3. 3Behind it sit the subnets of the whole site.
  2. Stage 1 · Lateral movementEnterprise ITMarch to July 2025

    Months inside the large plant, and its directory copied

    The large CHP plant was not attacked in a day. CERT Polska traces the first activity in its network to some time between March and May 2025, seven to nine months before the destruction. From an address on the FortiGate the attacker reached a jump hostA single hardened computer that remote users must log in to first, so every session into the plant passes through one controlled and recorded door. over remote desktopRemote Desktop Protocol: the Windows feature for using a computer’s screen, keyboard and mouse from somewhere else, and a favourite target when it is left open to the internet., helped by bookmarks that carried their own target credentials, and from the jump host reached the domain controllerThe server that runs Active Directory for a Windows domain and checks every login, which is why attackers aim for it first..

    In the second half of July the attacker dumped the full Active DirectoryThe Microsoft system that holds every user account, password and computer in a Windows domain, so whoever controls it controls every machine in it. database, the file that holds every account and password hash in the domain. Around a month after the domain controllerThe server that runs Active Directory for a Windows domain and checks every login, which is why attackers aim for it first. was reached, an encoded archive was unpacked with a built-in Windows tool, and the plant’s EDREndpoint detection and response: security software on each PC and server that watches for attacker behaviour, not just known viruses, and lets a team investigate and contain it. flagged what looked like a dump of credential memory. The record does not say what was done with that alert.

    With the directory in hand the attacker owned the plant’s Windows estate. Late in the year it came back for more reconnaissance and credential theftPulling passwords or login tokens out of a computer’s memory or files once an attacker controls it, to reuse them on other machines.. CERT Polska could not fully confirm that the two clusters of 2025 activity at this plant were the same actor.

    1. 1A VPN login lands on a jump host with saved remote-desktop logins.
    2. 2From there the attacker reaches the domain controller.
    3. 3In July the whole directory database is copied out.
  3. Stage 1 · Lateral movementControl networkDecember 2025

    A side door through a wind farm’s cellular network

    The second CHP plant, heating about 50,000 residents, was reached by a route CERT Polska says it had not seen in any known incident. The attacker started from a wind farm’s perimeter device, whose VPNVirtual private network: an encrypted tunnel over the internet that makes a remote computer behave as if it were plugged into the plant or office network. interface was reachable from the internet and accepted accounts defined in its configuration, and moved on to the farm’s Teltonika cellular router. The router’s logs show SSH logins during December and, most likely, SSH tunnelling into a private APN, a mobile-operator network reserved for the operator’s own devices.

    Beginning on 18 December the attacker repeatedly scanned the APN. On it sat a WAGO PFC200 controller whose web administration interface was reachable from the APN and still configured with the default credentials for its admin account. Through that controller the attacker reached the plant’s OT network and spent the week to 25 December mapping it. The investigation of this route took more than three months, which is why it appeared only in a follow-up report.

    A private APN feels internal because outsiders cannot dial into it. That is the trap: devices on it can reach one another, so one router at one farm becomes a doorway to a power plant miles away.

    “Treat the private APN as an untrusted network in relation to the OT environment.”

    Source 2: Energy Sector Incident Follow-up Report 2025
    1. 1A farm’s cellular router sits on a private APN shared with other sites.
    2. 2For a week the attacker scans the APN from that router.
    3. 3A controller with a default admin login opens a way into the CHP plant.
  4. Stage 2 · Execute ICS attackField devices29 December 2025, morning

    Field devices bricked through their factory logins

    On the morning of 29 December the plan against the renewable sites was set off, and recovered logs show it working through each site’s devices in ascending order of address. It did not need to be subtle: almost every device answered to a login its manufacturer had shipped with it. Three weeks earlier, on 8 December, the attacker had opened up the farms’ Windows HMIsHuman-machine interface: the operator screen or panel used to watch a process and adjust it, usually sitting in front of a PLC or a SCADA system., enabling administrative shares and adding a firewall rule named Microsoft Update.

    Hitachi RTU560 units, the remote terminal unitsRemote terminal unit: a small controller at an outlying site such as a pump station or substation that reports readings and takes commands over a telemetry link. that report each farm to the distribution operator and carry its commands, accepted a firmwareThe built-in software inside a device such as a PLC, switch or firewall, below the user programs, which the maker updates from time to time. upload through the default web account; the image had 240 bytes inserted at its entry point and sent the units into a reboot loop. Signed firmware updates were supported from version 13.2.1 but not enabled. Mikronika RTUs had their files deleted over default root SSH, two Hitachi Relion 650 relays lost system files over a default FTP account that the manufacturer’s recommended deployment disables, and every reachable Moxa serial server was reset, given a new password and pointed at 127.0.0.1. On the HMIsHuman-machine interface: the operator screen or panel used to watch a process and adjust it, usually sitting in front of a PLC or a SCADA system. a default administrator password let the wiperMalware whose only purpose is to destroy data or make computers unbootable, with no ransom and no way back except restoring from backup. run; HMIs whose password had been changed were not damaged.

    The farms could no longer talk to the distribution system operator or be controlled remotely. But the turbines and panels kept producing, and CERT Polska notes that losing all 30 sites at once would not have threatened the stability of the system.

    Inside the plant: The farms kept generating while their link to the distribution operator was down; the transmission operator said system stability was not affected (CERT Polska).

    “they did not affect the ongoing production of electricity”

    Source 3: Energy sector incident report, 29 December 2025 (summary)
    1. 1RTUs, relays and serial servers link each farm to the grid operator.
    2. 2Factory logins open them one by one: firmware, files, settings.
    3. 3The devices are bricked; the farms lose control but keep generating.
  5. Stage 2 · ImpactEnterprise IT29 December 2025

    A wiper by group policy at the large plant, stopped part-way

    At the large CHP plant the destruction used the plant’s own administration. The attacker put the wiperMalware whose only purpose is to destroy data or make computers unbootable, with no ransom and no way back except restoring from backup. on a network share and built a new group policyThe Active Directory feature for pushing settings or software to every computer in a domain at once, which attackers can abuse to spread malware the same way. from a copy of the Default Domain Policy, adding a scheduled task that ran the file as SYSTEM on every machine and then deleted itself. DynoWiper overwrites small blocks inside files and then deletes them. Antivirus did not flag it.

    More than 100 machines had run it when the plant’s EDREndpoint detection and response: security software on each PC and server that watches for attacker behaviour, not just known viruses, and lets a team investigate and contain it. stopped it, using canary files, decoysPlanting fake controllers, screens or files that no legitimate user would touch, so that anyone who does touch them reveals themselves as an intruder. that a wiperMalware whose only purpose is to destroy data or make computers unbootable, with no ransom and no way back except restoring from backup. reaches early. A slightly modified second attempt also failed. On servers the attacker booted a small Linux image to overwrite parts of the disks, and tried to change RAID settings. A private manufacturer, hit the same day, received a different wiper written in PowerShell, which CERT Polska assesses was likely generated with a large language model.

    CERT Polska is clear about the outcome: the attack on the plant did not achieve the attacker’s aim of disrupting heat supply to end users. One control, working as designed on the day, is the difference between a damaged IT estate and a city without heat in winter.

    “its operation was blocked by the EDR software used by the organization”

    Source 3: Energy sector incident report, 29 December 2025 (summary)
    1. 1The domain controller pushes a new group policy to every machine.
    2. 2A wiper runs as a SYSTEM task; over 100 machines are hit.
    3. 3EDR spots it through canary files and halts the rest.
  6. Stage 2 · Execute ICS attackField devices29 December 2025, from about 07:00

    Controllers stopped and locked at the smaller plant

    The attacker was inside the smaller plant’s network from about 05:30 to 10:10 on 29 December, nearly five hours, and began on the controllers at about 07:00. Its controllers, Siemens S7-300, S7-1200 and S7-1500 units, were reachable from the device the attacker had taken on the private APN. The record does not say how they were protected; it shows that the attacker could stop them and set a password of its own.

    The attacker set them to STOP, which shut down the steam turbine and the water treatment, and then password-protected them so that the plant’s engineers could not simply restart them. It factory-reset the plant’s seven Moxa serial servers and three switches, and tried ABB and Schneider drives, with unclear or failed results. Before leaving it corrupted the partition table of the WAGO controller it had used, and at the wind farm it reset the cellular router and the FortiGate to factory settings; the FortiGate’s logs were lost, while the router’s survived the reset.

    Recovery meant factory-resetting the controllers and restoring their programs from backups, which also erased the controllers’ own logs. The WAGO controller, a PFC200 with a built-in cellular modem, was damaged and yielded no recoverable data.

    1. 1Controllers run the plant’s steam turbine and its water treatment.
    2. 2From the APN the attacker sends STOP to each controller.
    3. 3Then it locks them with a password of its own; the turbine stops.
  7. Stage 2 · Response and recoveryPhysical processFrom 29 December 2025

    Generation goes on; devices replaced, the record published

    The attack was destructive by design; CERT Polska says all of it had a purely destructive objective. Yet the outcome is the reassuring part of this case. Wind and solar farms do not need remote control to generate: with the RTUsRemote terminal unit: a small controller at an outlying site such as a pump station or substation that reports readings and takes commands over a telemetry link. dead they kept producing, and the operator’s loss was visibility and control, not power.

    Recovery was physical work. Bricked RTUsRemote terminal unit: a small controller at an outlying site such as a pump station or substation that reports readings and takes commands over a telemetry link. and relays had to be replaced or reflashed, serial servers reconfigured, controllers restored from backups. At the smaller CHP plant those restores erased the controllers’ logs, and the attacker had already reset the router and firewall it used, wiping the firewall’s logs, which is part of why that investigation took more than three months.

    Poland went public quickly and in detail. The energy minister called it the strongest attack on the energy infrastructure in years; the Prime Minister alleged that everything indicated groups directly linked to foreign services. CERT Polska published the full timeline, malware analysis and indicators, so that every operator with the same devices could check its own.

    “Everything indicates that these attacks were prepared by groups directly linked to [foreign] services.”

    Source 4: Poland stops cyberattacks on energy infrastructure
    1. 1Bricked devices cut the farms off from the operator’s control room.
    2. 2Crews replace and reload them while the farms keep generating.
    3. 3The national CERT publishes the whole attack, with its indicators.

That is the record. Now the question each step raises:

Could you have stopped it?

Now you decide

Could you have stopped it?

The same steps, as decisions. At most steps you pick the control that would have stopped the attack at a cost a structured site can carry; at some you place the attacker on the plant map first, or spot the one control that does not act. A nuclear-grade answer at a water utility scores less than the right-sized one, because the money and the people are not infinite. Round 2 hands you a budget. “Would have stopped” means in this exercise’s judgement, with the control in place and working; the record rarely says what the operator actually had, and no control is a guarantee.

Step 1 of 7
0 / 21 shield 0 / 2 insight
Structured site · the band this exercise judges by

Grid-connected wind and solar farms that the distribution operator controls remotely, and a heat and power plant that heats almost half a million customers. Many farms are small on their own; together they are regional-utility infrastructure. A structured programme is the reasonable expectation, starting with the hygiene that would have closed most of these doors.

Target security levels come from the site's own IEC 62443-3-2 risk assessment; these bands are how the game judges what is proportionate. The reasoning under each answer says why a control is the right weight for this site.
01
Stage 1 · ExploitationIT to OT boundarySpring to December 2025

VPN logins that asked only for a password

  1. 1A firewall at the farm also runs the VPN, open to the internet.
  2. 2An account that needs only a password lets the attacker in.
  3. 3Behind it sit the subnets of the whole site.

VPN access with passwords alone on internet-facing firewalls

At the farms and at the CHP plants the way in was a FortiGate device acting as firewall and VPNVirtual private network: an encrypted tunnel over the internet that makes a remote computer behave as if it were plugged into the plant or office network. concentrator, with the VPN interface exposed to the internet and accounts that needed no second factor. At the large CHP plant CERT Polska found statically defined SSL-VPN accounts without two-factor authenticationMulti-factor authentication: a login that needs something more than a password, such as a code from a phone or a hardware key, so a stolen password alone is not enough., and logins through TorA network that hides where internet traffic comes from by bouncing it through several volunteer-run relays, used by attackers to stay anonymous. and from Polish and foreign addresses. Re-read this step in the story

What would have closed this door at an energy operator of this size?

02
Stage 1 · Lateral movementMarch to July 2025
Answer the step above

Months inside the large plant, and its directory copied

03
Stage 1 · Lateral movementDecember 2025
Answer the step above

A side door through a wind farm’s cellular network

04
Stage 2 · Execute ICS attack29 December 2025, morning
Answer the step above

Field devices bricked through their factory logins

05
Stage 2 · Impact29 December 2025
Answer the step above

A wiper by group policy at the large plant, stopped part-way

06
Stage 2 · Execute ICS attack29 December 2025, from about 07:00
Answer the step above

Controllers stopped and locked at the smaller plant

07
Stage 2 · Response and recoveryFrom 29 December 2025
Answer the step above

Generation goes on; devices replaced, the record published

Scoring: 3 points for the proportionate control, 2 for one that works but is heavier than this site needs, 1 for a control that helps, 0 for one that does not act at that step. In an odd-one-out step, 3 points for spotting the control that does not act. Plant-map questions earn insight points. Sources are listed at the end of the page. Jump to sources

Response and recovery

How they got back

Electricity production continued throughout. Field devices at the farms were replaced or restored, the smaller CHP plant’s controllers were factory-reset and reloaded from backups, and the large CHP plant’s EDREndpoint detection and response: security software on each PC and server that watches for attacker behaviour, not just known viruses, and lets a team investigate and contain it. contained the wiperMalware whose only purpose is to destroy data or make computers unbootable, with no ransom and no way back except restoring from backup.. CERT Polska published a full report with timeline, malware analysis and indicators on 30 January 2026, and a follow-up on the cellular route that recommends treating private APNs as untrusted, isolating the devices on them, changing default credentials and monitoring APN-to-OT traffic.

Take this to your plant

  • 1Default logins on field devices are not a hygiene detail. Almost every RTURemote terminal unit: a small controller at an outlying site such as a pump station or substation that reports readings and takes commands over a telemetry link., relay and serial server destroyed here opened with the password it shipped with, and the HMIsHuman-machine interface: the operator screen or panel used to watch a process and adjust it, usually sitting in front of a PLC or a SCADA system. whose password had been changed survived.
  • 2Distributed sites share configurations, and so share weaknesses. One reused VPNVirtual private network: an encrypted tunnel over the internet that makes a remote computer behave as if it were plugged into the plant or office network. password or one private APN can turn 30 sites into one target: give each site its own credentials and treat shared networks as untrusted.
  • 3Detection on the day still counts. EDREndpoint detection and response: security software on each PC and server that watches for attacker behaviour, not just known viruses, and lets a team investigate and contain it. with canary files stopped the wiperMalware whose only purpose is to destroy data or make computers unbootable, with no ransom and no way back except restoring from backup. at a plant heating almost half a million customers, after antivirus had missed it.

Sources

Where this record comes from

Government advisories, the victim's own statements, court and parliamentary records, and the technical reports of the teams that analysed the malware. Press is used only where no primary record exists, and is marked.

  1. 1
    Energy Sector Incident Report: 29 December 2025 CERT Polska, 2026 · Government report
  2. 2
    Energy Sector Incident Follow-up Report 2025 CERT Polska, 2026 · Government report
  3. 3
  4. 4
    Poland stops cyberattacks on energy infrastructure Chancellery of the Prime Minister of Poland, 2026 · Government statement
  5. 5
    DynoWiper update: technical analysis and attribution ESET, 2026 · Vendor technical report
  6. 6
  7. 7
  8. 8
  9. 9
Where the record is uncertain
  • Attribution is split, and every claim below is an allegation or an assessment. CERT Polska links the infrastructure to the cluster tracked as Static Tundra (Cisco), Berserk Bear (CrowdStrike), Ghost Blizzard (Microsoft) and Dragonfly (Symantec), a cluster the US FBI alleges belongs to a foreign intelligence service, though CERT Polska’s own report names no state; ESET attributes the wiper to Sandworm with medium confidence, and Dragos attributes the operation to ELECTRUM with moderate confidence. CERT Polska finds DynoWiper’s similarities to Sandworm wipers too weak to attribute.
  • How the attacker first obtained working VPN credentials for the farms is not stated. CERT Polska thinks it likely took administrative rights on the devices and with them the VPN credentials for all subnets.
  • The time inside is measured at the large CHP plant, where CERT Polska dates the first activity to between March and May 2025, and it could not fully confirm that the two clusters of 2025 activity there were the same actor. For the farms the first entry is not dated.
  • Officials differed on how close Poland came to a blackout. The deputy prime minister for digital affairs said “we were close to a blackout”; the Prime Minister said critical infrastructure was not threatened at any point. CERT Polska notes that losing all 30 farms at once would not have affected system stability.

Talk to RelyBlue

Which of these doors is open in your plant?

An assessment that starts from the attacks that actually happened, scoped to what a site like yours should carry.

  • You talk to a senior advisor, never a salesperson