March to July 2026 · Water and wastewater, energy, local government · United States

US utility controller attacks 2026

From March 2026 attackers reached water, energy and municipal controllers that answered on the open internet, copied their programs and changed them, in one case overriding the logic that kept a process within safe limits; six US agencies allege the attackers are state-affiliated. Over two days in July, in attacks not formally attributed, more than 30 Minnesota water systems were hit.

Allegedly state-backedWay in: Device exposed to the internetProcess manipulatedBaseline site

What happened

The short version

Since at least March 2026, attackers that six US agencies allege are state-affiliated have been reaching programmable logic controllersProgrammable logic controller: the rugged industrial computer wired to sensors and actuators that runs the automatic control of a machine or process. at water and wastewater systems, energy sites and local municipalities, where the controllers answered directly on the internet. Using the manufacturers’ own engineering software from leased servers abroad, they copied the controllers’ project files, changed or deleted logic, manipulated what operators saw on their screens and, at one victim, loaded logic that overrode the instructions keeping the process within safe limits. In a few cases this caused operational disruption and financial loss.

On 26 and 27 July more than 30 community water systems in Minnesota were hit. Controllers had their passwords and addresses changed, locking operators out of monitoring and in some cases control; Braham’s water plant went offline for about three hours, and other towns ran by hand. Within days the FBI and EPA counted incidents in at least seven states, with effects that included loss of pressure and flooding, and CISAThe US Cybersecurity and Infrastructure Security Agency, the government body that publishes advisories and guidance for critical infrastructure. reported boil water notices and sustained manual operations.

Key dates

  1. PreparationMarch 2026Citing Middle East activity, the EPA urges water systems to strengthen their cybersecurity; the agencies later date the controller attacks to at least March
  2. Way inFrom March 2026Internet-facing controllers are reached from leased servers abroad; project files are copied and altered
  3. Response7 April 2026Six agencies publish advisory AA26-097A on actors exploiting controllers, alleging they are state-affiliated
  4. Response22 July 2026The advisory is updated: Siemens and Schneider controllers targeted too, and safety logic overridden at one victim
  5. Impact26 to 27 July 2026More than 30 Minnesota community water systems are hit over two days
  6. Aftermath30 July 2026The FBI and EPA report incidents in at least seven states; CISAThe US Cybersecurity and Infrastructure Security Agency, the government body that publishes advisories and guidance for critical infrastructure. urges utilities to take controllers off the internet

How did that happen

The way in, and the way through

The common factor was exposure. The controllers, Rockwell CompactLogix, Micro850 and MicroLogix units and later Siemens S7-1200 and Schneider Modicon M340, were reachable from the internet on their native ports, in some cases through cellular modems installed for remote access. The actors connected from overseas addresses with the vendors’ engineering software running on leased, third-party hosting, and deployed Dropbear, a small SSH server, on victim devices.

Once connected they extracted project files, edited logic and the reusable blocks it is built from, and downloaded it back; the July update describes changes that disabled critical shutdown and alarm logic. In the July wave the actors switched on the controllers’ password protection with passwords of their own and changed their IP addresses, cutting operators off. The advisory describes controllers installed and deployed without sufficient network or hardening controls.

The path through the plant, step by step (the numbers are the steps told below)

Attribution: Actors that six US agencies allege are state-affiliated (joint advisory AA26-097A by the FBI, CISA, NSA, EPA, DOE and US Cyber Command; not tested in court). The late-July wave against water systems has not been formally attributed

The sequence of events

How it unfolded, step by step

The record in order, from the first foothold to the recovery. Each step says what was done, how it worked, what it looked like from inside the plant, and where the attacker was in the plant at that moment. Read this first; the game that follows asks what would have stopped each step.

  1. Stage 1 · ReconnaissanceInternetFrom March 2026

    Controllers answering on the open internet

    The campaign did not need a clever way in. Programmable logic controllersProgrammable logic controller: the rugged industrial computer wired to sensors and actuators that runs the automatic control of a machine or process., the small industrial computers that run pumps, valves and chemical dosing, were reachable directly from the internet at water systems, energy sites and municipal facilities. They are found the way attackers always find such devices: by scanning for the ports their engineering software speaks.

    The advisory names the products: Rockwell Automation’s CompactLogix and Micro850 in April, with Siemens S7-1200 and Schneider Electric’s Modicon M340 added in July, on the ports their engineering software uses. The actors came from several overseas addresses on leased hosting, and the agencies published those addresses so that every operator could check its own logs.

    For a small utility, a controller on the internet usually means convenience: an integrator or an operator wanted to check the plant without driving to it. It also means that anyone who can find it can talk to it.

    “installed and deployed without sufficient network and/or hardening security controls”

    Source 1: Joint advisory AA26-097A on attacks on programmable logic controllers across US critical infrastructure (7 April 2026)
    1. 1Controllers at small utilities answer on their native ports, online.
    2. 2Leased servers abroad look for exactly those ports.
    3. 3Every controller that answers becomes a target.
  2. Stage 1 · Command and controlIT to OT boundaryMarch to July 2026

    Cellular modems that go around the firewall

    Not every path ran through the utility’s firewall. Cellular modems that operators, vendors or system integrators install for remote access are a path that runs around it, and CISAThe US Cybersecurity and Infrastructure Security Agency, the government body that publishes advisories and guidance for critical infrastructure. warns that such modems may not be documented or included in routine scans of what a utility has exposed.

    The advisory describes the actors deploying Dropbear, a small SSH server, on victim endpoints; LevelBlue’s review notes that in one case they used it on a victim’s modem to establish remote access. LevelBlue also cites the FBI’s observation that common network configurations supplied by third-party providers appeared across multiple victims. A shared configuration means a shared weakness: what opens one site opens the next.

    The agencies’ answers are plain: secure the modems, turn on their logs to detect intrusion, and put a gateway, firewall or VPNVirtual private network: an encrypted tunnel over the internet that makes a remote computer behave as if it were plugged into the plant or office network. in front of each controller.

    1. 1A cellular modem added by an integrator sits beside the controller.
    2. 2The actors reach it over the mobile network and log in by SSH.
    3. 3They leave their own SSH server on it: a way in that stays.
  3. Stage 1 · ExploitationField devicesMarch to July 2026

    The vendor’s own software connects, and the program is copied

    To a controller, the vendor’s engineering software is the most trusted client there is: it is how engineers load and change the program. The actors used exactly that, running Studio 5000 Logix Designer and the equivalent tools from leased servers, and the controllers accepted the connections.

    The first thing they took was the project file, which holds the ladder logicThe graphical programming language used in most PLCs, drawn as rungs of a ladder that mimic the relay wiring diagrams electricians know. and the configuration, a complete description of what the controller does and how. The agencies describe the files being copied to infrastructure the actors controlled.

    Several of these controller families support a password that must be given before the program is read or changed. In the July wave the FBI describes the actors turning that protection on themselves and setting their own passwords, which locked operators out. Where the owner had set it first, a stranger’s engineering session would have had nothing to work with.

    “The actors used leased, third-party hosted infrastructure with configuration software”

    Source 1: Joint advisory AA26-097A on attacks on programmable logic controllers across US critical infrastructure (7 April 2026)
    1. 1The actors open the vendor’s engineering software on a leased server.
    2. 2The controller accepts the connection; nothing asks who it is.
    3. 3Its project file, logic and settings, goes out to the actors.
  4. Stage 2 · Execute ICS attackField devicesMarch to July 2026

    Logic rewritten: shutdowns and alarms disabled, screens falsified

    Copying a program is espionage; changing it is sabotage. The agencies describe the actors modifying or deleting logic, including Add-On Instructions, the reusable blocks engineers build their programs from, and manipulating the values displayed on HMIHuman-machine interface: the operator screen or panel used to watch a process and adjust it, usually sitting in front of a PLC or a SCADA system. and SCADASupervisory control and data acquisition: the software and screens that let operators watch and control equipment spread across a site or a region from one place. screens, so that what operators saw was not what the process was doing.

    At one US victim the FBI observed the actors download a malicious project to a controller using its configuration software. The new logic overrode the instructions responsible for keeping the process within safe operating parameters; the updated advisory says such changes disabled critical shutdown and alarm logic, allowing systems to enter unsafe conditions.

    Among the advisory’s immediate steps is one of the cheapest controls in industrial security: put the controller’s physical mode switch in RUN, to prevent remote modification, and switch back as soon as planned work is done. The FBI repeats it. A controller in RUN refuses a new program from anyone.

    “added logic that overrode specific instruction sets responsible for maintaining safe operating parameters”

    Source 2: AA26-097A, updated 22 July 2026
    1. 1The controller runs the plant’s logic, alarms and shutdowns included.
    2. 2A modified program is downloaded from the actors’ software.
    3. 3Alarms and shutdowns are overridden; screens show what they choose.
  5. Stage 2 · ImpactPhysical process26 to 27 July 2026

    Two days: controllers locked at more than 30 water systems

    Sunday 26 and Monday 27 July were different in scale. Minnesota IT Services reported a coordinated attack on the operational technologyOperational technology: the hardware and software that monitors and controls physical equipment, as opposed to the office IT that handles information. of more than 30 community water systems and activated the state’s incident response. On 30 July the FBI and EPA warned that utilities in at least seven states had reported similar incidents since 27 July, and named Rockwell’s MicroLogix 1100 and 1400 controllers exposed to the internet.

    This wave did not need to rewrite logic. The actors changed the controllers’ IP addresses and switched on password protection with their own passwords, which cut operators off from monitoring and, in some cases, from control. The FBI says effects included loss of pressure and flooding, and warns that lost pressure can let untreated groundwater seep into pipes; CISAThe US Cybersecurity and Infrastructure Security Agency, the government body that publishes advisories and guidance for critical infrastructure. reported boil water notices and sustained manual operations. At Braham, LevelBlue reports, the controls for the municipal well and treatment plant were disabled; in Plymouth, cellular links to two water towers and several wastewater lift stations were disrupted.

    The state stressed that being affected did not mean every community’s water service was disrupted, and knew of no requests for residents to change their water use. It has not attributed the activity, and the FBI and EPA announcement named no actor.

    Inside the plant: Braham said its water plant was offline for an unknown reason, then about three hours later back online and treating water as expected; it later blamed a malicious cyberattack by unknown actors (city, via BleepingComputer).

    1. 1Small town water systems run on controllers reachable online.
    2. 2Over two days the controllers’ passwords and addresses are changed.
    3. 3Operators lose sight and control; towns switch to running by hand.
  6. Stage 2 · Response and recoveryField devicesFrom 30 July 2026

    Off the internet, reloaded from copies, and a national warning

    The response ran on two levels. Locally, utilities took controllers off the internet, reset passwords and addresses, and reloaded programs, which is quick where an offline copy of the logic exists and slow where the only copy was in the controller that had just been changed. CISAThe US Cybersecurity and Infrastructure Security Agency, the government body that publishes advisories and guidance for critical infrastructure. told operators to keep a known clean backup of each controller’s image in case a modified password locks them out, and the FBI and EPA to check a backup for malicious logic before restoring it.

    Nationally, the agencies kept publishing. The April advisory was updated in July with more controller makes and guidance on finding malicious changes in reusable code; on 30 July the FBI and EPA warned of incidents in at least seven states and CISAThe US Cybersecurity and Infrastructure Security Agency, the government body that publishes advisories and guidance for critical infrastructure. urged the water sector to take its controllers off the internet as soon as possible. Minnesota’s own guidance reads like a baseline programme: no unnecessary internet access, unique passwords, MFAMulti-factor authentication: a login that needs something more than a password, such as a code from a phone or a hardware key, so a stolen password alone is not enough. on remote access, separate OT networks, an inventory of OT and its connections, offline backups and tested plans.

    None of it is new. The same agencies gave much the same advice after the Aliquippa attack in 2023. What changed in 2026 was the scale, and an adversary willing to override safety logic.

    1. 1Utilities pull controllers off the internet and reset them.
    2. 2Programs are reloaded from copies, where copies exist.
    3. 3Advisories tell every utility what to check and what to close.

That is the record. Now the question each step raises:

Could you have stopped it?

Now you decide

Could you have stopped it?

The same steps, as decisions. At most steps you pick the control that would have stopped the attack at a cost a baseline site can carry; at some you place the attacker on the plant map first, or spot the one control that does not act. A nuclear-grade answer at a water utility scores less than the right-sized one, because the money and the people are not infinite. Round 2 hands you a budget. “Would have stopped” means in this exercise’s judgement, with the control in place and working; the record rarely says what the operator actually had, and no control is a guarantee.

Step 1 of 6
0 / 18 shield 0 / 1 insight
Baseline site · the band this exercise judges by

The victims were water systems, energy sites and municipalities whose controllers answered on the internet, exactly the sites a proportionate programme starts with hygiene for. Every control the agencies asked for first is a baseline one: controllers off the internet, passwords set, mode switches in RUN, offline copies of the logic.

Target security levels come from the site's own IEC 62443-3-2 risk assessment; these bands are how the game judges what is proportionate. The reasoning under each answer says why a control is the right weight for this site.
01
Stage 1 · ReconnaissanceFrom March 2026

Controllers answering on the open internet

  1. 1Controllers at small utilities answer on their native ports, online.
  2. 2Leased servers abroad look for exactly those ports.
  3. 3Every controller that answers becomes a target.

Finding controllers that answer on the internet

The advisory describes Rockwell Automation CompactLogix and Micro850 controllers, and later Siemens S7-1200 and Schneider Electric Modicon M340 units, reachable from the internet on their native ports, 44818, 2222, 102 and 502, and SSH on 22. The actors reached them from several overseas addresses on leased, third-party hosting. Re-read this step in the story

Before the control: where in the plant was the attacker at this step? 1 insight point

02
Stage 1 · Command and controlMarch to July 2026
Answer the step above

Cellular modems that go around the firewall

03
Stage 1 · ExploitationMarch to July 2026
Answer the step above

The vendor’s own software connects, and the program is copied

04
Stage 2 · Execute ICS attackMarch to July 2026
Answer the step above

Logic rewritten: shutdowns and alarms disabled, screens falsified

05
Stage 2 · Impact26 to 27 July 2026
Answer the step above

Two days: controllers locked at more than 30 water systems

06
Stage 2 · Response and recoveryFrom 30 July 2026
Answer the step above

Off the internet, reloaded from copies, and a national warning

Scoring: 3 points for the proportionate control, 2 for one that works but is heavier than this site needs, 1 for a control that helps, 0 for one that does not act at that step. In an odd-one-out step, 3 points for spotting the control that does not act. Plant-map questions earn insight points. Sources are listed at the end of the page. Jump to sources

Response and recovery

How they got back

Utilities took exposed controllers off the internet, reset passwords and addresses, reloaded programs and ran by hand where needed. Advisory AA26-097A, first published on 7 April 2026, was updated on 22 July with Siemens and Schneider controllers and guidance on detecting malicious changes in Rockwell Add-On Instructions. On 30 July the FBI and EPA issued a public service announcement on MicroLogix controllers and CISAThe US Cybersecurity and Infrastructure Security Agency, the government body that publishes advisories and guidance for critical infrastructure. urged the water sector to remove exposed controllers from the internet; Minnesota issued baseline guidance to its water systems.

Take this to your plant

  • 1If a controller answers on the internet, assume someone has already found it. Taking it off is the cheapest fix in this library, and the agencies have been asking for it since Aliquippa in 2023.
  • 2Leave the key in RUN and switch the controller’s own password on. Together they turn a remote program change into something that needs a person at the cabinet and a password the attacker does not have.
  • 3Keep an offline copy of every controller’s program, and practise running by hand. Together they turn a locked controller into an inconvenience.

Sources

Where this record comes from

Government advisories, the victim's own statements, court and parliamentary records, and the technical reports of the teams that analysed the malware. Press is used only where no primary record exists, and is marked.

  1. 1
  2. 2
    AA26-097A, updated 22 July 2026 FBI, CISA, NSA, EPA, DOE, US Cyber Command and the Treasury, 2026 · Government advisory
  3. 3
  4. 4
  5. 5
  6. 6
  7. 7
  8. 8
  9. 9
  10. 10
    EPA alert: water systems should strengthen cybersecurity in light of activities in the Middle East US Environmental Protection Agency, Office of Water, 2026 · Government alert
Where the record is uncertain
  • The agencies allege that the activity described in AA26-097A is the work of state-affiliated actors and refer to earlier controller attacks by CyberAv3ngers, without naming the group behind the 2026 activity. Minnesota has not attributed the July wave and the FBI and EPA announcement names no actor.
  • Whether the July changes to passwords and addresses and the logic changes described in the advisory were the work of the same actors is not established.
  • The number of victims is not public. Minnesota counts malicious activity at more than 30 community water systems and says that does not mean every affected community lost service; the FBI and EPA count utilities in at least seven states.
  • Town-level details come from city statements as reported by the press and from LevelBlue’s review, not from the agencies.

Talk to RelyBlue

Which of these doors is open in your plant?

An assessment that starts from the attacks that actually happened, scoped to what a site like yours should carry.

  • You talk to a senior advisor, never a salesperson